# 3- to 1-phase switching with Zaptec Go 2

> ✅ Zaptec Go 2 chargers support switching between three-phase and one-phase charging.
>
> * The charger must be wired with 3 phases and be part of a three phase installation
> * The charger must be online
> * The charger must not be in standalone mode
> * The charger must not have OCPP 1.6J Native authentication enabled

## Automatic switching behavior using Zaptec power management

### When starting a charging session

* If the **Available current** on all three phases is above the **3 to 1-phase switch current**, the charger will commence charging on all three phases.
* Else, the charger will commence charging on one phase, using the phase connected to the charger's L1 terminal.

### During a charging session

* If the **Available current** on any phase drops below the **3 to 1-phase switch current**, the charger will switch from three phase to one phase, and resume charging on the phase connected to the charger's L1 terminal.
* If **Allow chargers to return to three phase charging** is enabled and the **Available current** on all phases rises above the **3 to 1-phase switch current**, the charger will resume charging on all three phases.

<Callout icon="fa-triangle-exclamation" theme="warning">
  Some vehicles are unable to successfully switch from one-phase to three-phase charging during a session. If the charging circuit breaker operates, this feature must be disabled.
</Callout>

* There is a limit on the number of times during a session that charging can be switched back to three phase. This is set by **Switches** **allowed before** **locking to single phase**.

*The default limit is 5. The maximum limit is 20.*

<Callout icon="fa-triangle-exclamation" theme="warning">
  **Go 2 – Mechanical Switching Limit**

  The Zaptec Go 2 has a mechanical switching limit of _20 switching operations per charge session._

  Phase switching temporarily interrupts charging.
  Each such interruption increases the mechanical switching counter, including 3-phase ↔ 1-phase switching.

  Once the limit is reached, the charging session is terminated with a warning.

  _Related warning_

  In scenarios with frequent start/stop events, the charger may trigger the warning:

  `WARNING_MAX_SESSION_RESTART`

  This warning indicates that the charging session has experienced an unusually high number of restarts within a short period of time. This can typically occur due to repeated interruptions, for example caused by phase switching or vehicle behavior.
</Callout>

## Controlling phase switching behavior in the Zaptec Portal

The Installation settings can be found in the Zaptec Portal under **Installation > Settings > Power management**.
The Charger settings can be found in the Zaptec Portal under **Charger > Settings**.

**To enable automatic 3- to 1-phase switching**

* Set Installation **3 to 1-phase switch current** to a value between 6A and 31A (default 8A)
* Set Charger **Max phases** to 3

**To enable automatic 1- to 3-phase switching**

* Check Installation **Allow chargers to return to three phase charging**

**To adjust the automatic 3- to 1-phase switching threshold**

* Set Installation **3 to 1-phase switch current** to the desired value

<Callout icon="fa-triangle-exclamation" theme="warning">
  To avoid repeated switching between one phase and three phases when charging from solar, the switching threshold should be set to a value _above_ the maximum expected solar charging current. For example, for a 3-phase 6kW solar array, set this value to `Maximum current per phase = 6000W / (230V × 3) ≈ 9A`. In this case, setting the threshold to 9 will ensure that single-phase mode is always used when solar charging.

  If the maximum expected solar charging current is unknown, we recommend setting this value to 8A.
</Callout>

**To disable 3- to 1-phase switching at the installation level (and always make three phases available to the chargers)**

* Set Installation **3 to 1-phase switch current** to 0A

**To disable 1- to 3-phase switching at the installation level (and only make one phase available to the chargers)**

* Set Installation **3 to 1-phase switch current** to 32A

**To disable phase switching at the charger level and always charge with one phase**

* Set Charger **Max phases** to 1

## Controlling phase switching behavior with the Zaptec API

Charger **Max phases** must be set to 3 in the Zaptec Portal, as described above.

* **To allow chargers to return to 3-phase charging during a session**, **Allow chargers to return to three phase charging** must be enabled in the Zaptec Portal, as described above.
* **To ensure a stable charging experience**, we recommend updating these settings no more than once every 15 minutes. Frequent changes may cause the vehicle to interrupt the charging session.
* **To control the phase switching behaviour dynamically**, you can use the Zaptec API to update the installation settings. This will allow the Zaptec load balancer to act based on the values set.
  Refer to the [official documentation](https://docs.zaptec.com/reference/api_chargehistory_get#/) for a detailed description of the API endpoints.
* **To charge with three phases**
  Use `https://api.zaptec.com/api/installation/{id}/update` to set **threeToOnePhaseSwitchCurrent** to 0.
* **To charge with one phase**
  Use `https://api.zaptec.com/api/installation/{id}/update` to set **threeToOnePhaseSwitchCurrent** to 32.
* **To allow the Zaptec load balancer to automatically select 1- or 3-phase charging**
  Use `https://api.zaptec.com/api/installation/{id}/update` to set **threeToOnePhaseSwitchCurrent** to a value between 6 and 31.

<Callout icon="fa-triangle-exclamation" theme="warning">
  To avoid repeated switching between one phase and three phases when charging from solar, the switching threshold should be set to a value _above_ the maximum expected solar charging current. For example, for a 3-phase 6kW solar array, set this value to `Maximum current per phase = 6000W / (230V × 3) ≈ 9A`. In this case, setting the threshold to 9 will ensure that single-phase mode is always used when solar charging.

  If the maximum expected solar charging current is unknown, we recommend setting this value to 8.
</Callout>